Static Ground Monitoring System
The “Static Grounding Monitoring System” functions as a part of Overfill Protection & Earthing System.
The Static Grounding Monitoring Systems provide a visual green light indicating a confirmed grounding condition of the vehicles during the transfer of flammable and combustible materials. A red light indicates the absence of a dependable ground. An interlock circuit within the Static Grounding Monitoring Systems will prevent pumps and equipment from starting until a satisfactory ground is established. The interlock circuit will also shut off pumps and equipment if the ground is lost during the pumping operation.
Specifications
Input Power: | 85VAC to 250VAC 50Hz |
Input Current: | <60mA |
Output Signal: | On-Off signal |
Monitoring Set Point: | 10 ohms |
Alarm: | Visible alarm |
Spiral Cable: | Extendable to 5.3m (17.4ft.) |
Output Safety Parameters: | Um:250VAC, Uo:14.28VDC, Io:27.2mA, Po:97mW, Co:4.17μF, Lo:192mH |
Indicator: | Lamp (Green=satisfactory ground and red=no ground) |
Ambient temperature: | -20℃ to +55℃(-4℉ to +131℉) |
EU-Type Examination Certification No.: | Presafe 16 ATEX 8909X |
QAN Certificate No.: | Presafe 16 ATEX 7744Q |
Standard: | EN60079-0,EN60079-1, EN60079-11 |
ApplicableDirective: | 2014/34/EU |